Construction data NFA2X / SAH-VO 0.6/1 kV
|
Number of conductors
and nominal cross
section
|
Diameter of bundle approx.
|
Mass of Al cores approx.
|
Cable weight approx.
|
Allowed current in power supply networks
|
Allowed current at short-circuit
|
N x mm2
|
mm
|
kg/km
|
kg/km
|
A
|
kA
|
1x1b
|
9,0
|
44
|
74
|
81
|
0,8 |
1x25
|
10,0
|
67
|
103
|
107
|
1,3
|
1x35
|
11,0
|
97
|
133
|
132
|
1,9
|
1x50
|
12,5
|
137
|
185
|
162
|
2,7
|
1x70
|
14,0
|
187
|
242
|
205
|
3,8
|
1x95
|
16,0
|
267
|
333
|
245
|
5,2
|
2x16
|
18,0
|
91
|
152
|
81
|
0,8
|
2x25
|
20,0
|
139
|
210
|
107
|
1,3
|
2x35
|
22,0
|
196
|
272
|
132
|
1,9
|
2x50
|
25,0
|
281
|
277
|
162
|
2,7
|
4x16
|
19,0
|
181
|
303
|
81
|
0,8
|
4x25
|
20,0
|
278
|
421
|
107
|
1,3
|
4x35
|
25,0
|
397
|
543
|
132
|
1,9
|
4x50
|
28,0
|
562
|
753
|
162
|
2,7
|
4x70
|
32,0
|
764
|
986
|
205
|
3,8
|
4x95
|
44,0
|
1091
|
1358
|
243
|
5,2
|
4x25+1x16
|
25,0
|
323
|
496
|
107
|
1,3
|
4x25+2x16
|
28,0
|
368
|
572
|
107
|
1,3
|
4x35+1x16
|
28,0
|
442
|
619
|
132
|
1,9
|
4x35+2x16
|
31,0
|
487
|
695
|
132
|
1,9
|
4x35+1x25
|
29,0
|
453
|
645
|
132
|
1,9
|
4x35+2x25
|
32,0
|
536
|
754
|
132
|
1,9
|
4x50+1x16
|
30,0
|
607
|
829
|
162
|
2,7
|
4x50+2x16
|
34,0
|
652
|
905
|
162
|
2,7
|
4x50+1x25
|
31,0
|
631
|
858
|
162
|
2,7
|
4x50+2x25
|
35,0
|
700
|
964
|
162
|
2,7
|
4x50+1x35
|
32,0
|
661
|
889
|
162
|
2,7
|
4x50+2x35
|
36,0
|
760
|
1025
|
162
|
2,7
|
4x70+1x16
|
35,0
|
810
|
1061
|
205
|
3,8
|
4x70+2x16
|
38,0
|
855
|
1137
|
205
|
3,8
|
4x70+1x25
|
36,0
|
834
|
1091
|
205
|
3,8
|
4x70+2x25
|
38,0
|
903
|
1196
|
205
|
3,8
|
4x70+1x35
|
36,0
|
854
|
1121
|
205
|
3,8
|
4x70+2x3!)
|
40,0
|
963
|
1257
|
205
|
3,8
|
4x95+1)0(3
|
41,0
|
1136
|
1434
|
245
|
5,2
|
4x95+2x16
|
44,0
|
1181
|
1510
|
245
|
5,2
|
4x95+1x25
|
42,0
|
1160
|
1463
|
245
|
5,2
|
4x95+2x25
|
45,0
|
1230
|
1569
|
245
|
5,2
|
4x95+1x35
|
42,0
|
1190
|
1494
|
245
|
5,2
|
4x95+2x35
|
46,0
|
1289
|
1630
|
245
|
5,2
|
|