Uo/U  -  6/10 kV IEC 60502-2, IEC 60332-3
Cu/Al conductors•XLPE insulation•Cu screen•PVC sheath•Armour Al wires•PVC sheath flame retardant
Applicaion
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10 kV and frequency 49 Hz to 61 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants.
 
The cables are manufactured with sheaths of flame retardant materials
They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
 
 
Cable construction
Construction
According to IEC 60502-2
Conductor
Cu or Al stranded compacted,
according to IEC60228 class 2
Inner semi-
conductive layer
semi-conductive XLPE compound
Insulation
XLPE compound
Outer semi-
conductive layer
semi-conductive XLPE compound
Metal screen
-I option - Cu tapes
laid with overlap over each phase
-II option - Cu wires laid concentrically
Separating layer
PVC compound -flame retardant
Armour
Al wires laid concentrically
Sheath
PVC compound -- flame retardant
Color
black or red
Technical data
Conductor resistance at 20oC
According to IEC 60228 class 2
Max. conductor temperature
90°C continuous operation
Overload temperature
130°C /1 OOh/per year max./
Short circuit temperature
250°C /5 s max./
Nominal voltage Uo/U
6/10 kV
Highest system voltage Uo/U, no more than
12 kV
Test voltage AC (~) - 5 min
Level of partial discharge at 2*Uo:
6/10 kV 21kV 67 kV
max5pC
Bending radius, min
Bending radius adjacent to
joints or terminations,     min
15x D cable 12x D cable
Temperature of laying
no less than -5°C
Ambient temperatures
- 30 to 50°C
Tests: Flame retardancy
IEC 60332-3 Kat B(3.5l/m)and C(1.5l/m)
  
 Construction data 2XSYRaY-FR, A2XSYRaY-FR 6/10kV
Number of cond. and nominal   cross section
Thickness of insulation
 
 
Diameter of Al wires
-for armor
sheath
Cable
diameter approx.
2XSYRaY-FR
A2XSYRaY-FR
Mass of Cu appr.
Cable weight approx.
Mass of Al appr.
Cable weight approx.
N x mm2
mm
mm
mm
mm
kg/km
kg
kg/km
kg
6/10kV
 
 
 
 
 
 
 
 
1x50 rm
3.4
1.6
1.8
27.4
520
1200
130
810
1x70 rm
3.4
1.6
1.9
29.2
720
1500
190
970
1x95 rm  3.4 1,6 1,9 30.9 960 1800 260 1100
1x120rm 3.4 1.6 2.0 32.5 1200 2100 330 1200
1x150rm
3.4
2.0
2.1
34.9
1465
2550
405
1490
1x185rm
3.4
2.0
2.1
36.6
1795
2950
510
1665
1x240rm
3.4
2.0
2.2
39.2
2325
3600
665
1940
1x300rm
3.4
2.0
2.2
41.4
2925
4250
830
2155
1x400rm
3.4
2.0
2.4
44.6
3750
5180
1060
2490
1x500rm
3.4
2.5
2.5
49.2
4740
6550
1410
3220