Home  »  Power cables, flame retardant  »  Power cables middle voltage,flame retardant  »  2XSEYBY - FR A2XSEYBY - FR

2XSEYBY - FR A2XSEYBY - FR

Uo/U  6/10 kV IEC 60502-2 , IEC 60332-3
Cu / Al conductors • XLPE insulation • Cu screen • Armour st. tapes • PVC sheath flame retardant
Application
The three-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10 and frequency 50 Hz in urban and district electrical networks and for electrical supply of transformer's substations, small and medium industrial plants.
 
The cables are manufactured with
sheaths of flame retardant materials.
They are suitable for use in distribution installations, electric power stations and industrial systems.
The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter.
Cable construction
Construction
according to IEC 60502 -2
Conductor
Cu and Al stranded compacted,
according to IEC 60228 class 2
Inner semi- conductive layer semi-conductive XLPE compound
Insulation
XLPE compound
Outer semi- conductive layer semi-conductive XLPE compound
Metal screen over
each phase -I option - Cu tapes laid with overlap over each phase
Metal screen
-II option - Cu wires laid concentrically
Cable assembly
Three insulated and screened phases are twisted with
fillings and tape support
Inner sheatth
I -option - exstruded PVC compound flame retardant -
(bedding)
kat A
II-option - exstruded PVC compound - kat B and C
Armour
two steel tapes or two steel galvanized tapes
Sheath
PVC compound flame retardant
Color
Black or red
Technical data
Conductor resistance at 20oC
According to IEC 60228
Max. conductor temperature
90°C continuous operation
Overload temperature
130°C  /100h/per year max/
Short circuit temperature
250°C /5 s max./
Nominal voltage Uo/U
6/10 kV
Highest system voltage Um, no more than
6/10 kV 12 kV
Test voltage Uo/U
AC (~) - 5 min
DC (=) - 15 min
6/10 kV
21 kV
67 kV
Level of partial discharge at 2*Uo
max. 5 pC
Bending radius, min.
- 15x D cable
Temperature of laying
no less than -5°C
Temperature of exploitation
- 30 to 50°C
Tests
according to IEC 60 502-2
Flame retardant
IEC 602332-3, Kat A - 7l/m Kat B(3.5l/m)and C(1.5l/m)
  
Construction data 2XSEYBY-FR, A2XSEYBY-FR 6/10
Number of
cond. and
nominal
cross section
Thickness of insulation|
Thickness of sheath
Nominal cross-sec­tion of screen
Cable diameter approx.
2XSEYBY-FR
A2XSEYBY-FR
Mass of Cu appr.
Cable weight approx.
Mass of Al appr.
Cable weight approx.
 
mm
mm
mm
mm
kg/km
kg
kg/km
kg
6/10kV
 
 
 
 
 
 
 
 
3x35rm/16
3,4
2,5
16
48.4
1010
3639
298
2963
3x50rm/16
3,4
2,6
16
51.0
1363
4203
404
3292
3x70rm/16  3,4 2,7 16 55.0 1968  5117  584 3803 
3x95rm/16
3,4
2.9
16
59.3
2732
6239
809
4412
3x120rm/16
3,4
3.0
16
62.5
3440
7178
1023
4882
3x150rm/25
3,4
3.1
25
66.4
4245
8433
1257
5595
3x185rm/25  3,4 3.2 25 70.5 5311  9831  1579  6285 
3x240rm/25
3,4
3.4
25
76.3
6981
12001
2071
7337
3x300rm/25
3,4
3.7
25
83.2
8661
15023
2589
9255