2XSEY- FR A2XSEY-FR

Uo/U  -  6/10 kV IEC 60502-2, IEC 60332-3
Cu/Al conductors • XLPE insulation • Cu screen • PVC sheath - flame retardant
Application
The three-core cables flame retardant with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10 kV and frequency 50 Hz. The cables are manufactured with sheaths of flame retardant materials.
 
They are suitable for use in distribution installations, electric power stations and substations for fixed indoor assembly in cable ducts and conduits, over shelves and grilles. They should not be laid directly underground or in water. The cables should not be laid in or near nuclear stations.
 
Cable construction
Construction
According to IEC 60502-2
and IEC 60332-3
Conductor
Cu and Al stranded compacted wires
 
to IEC 60228 cl.2
Inner semi-
conductive layer
semi-conductive XLPE compound
Insulation
XLPE compound
Outer semi-
conductive layer
semi-conductive XLPE compound
and semi-conductive tape
Metal screen
-I option - Cu tapes laid with overlap
over each phase
-II option - Cu wires laid concentrically
Cable assembly
three insulated and screenesd
phases are twisted with and
tape support
Inner sheath
I -option - fillings and sheat -
exstruded PVC compound flame
retardant - kat A
II-option - fillings and tapes -
kat B and C
Sheath
PVC compound flame retardant
Color
black
Technical data
Conductor resistance at 20oC
According to IEC 60228
Max. conductor temperature
90°C continuous operation
Overload temperature
130°C /1 OOh/per year max./
Short circuit temperature
250°C /5 s max./
Nominal voltage Uo/U
6/10 kV
Highest system voltage Uo/U, no more than
6/10 kV 12 kV
Test voltage
AC - 5 min.
AC (~) - 5 min
DC (=) - 15 min
 
6/10 kV
21 kV
67 kV
Bending radius, min.
- 15x D cable
Temperature of laying
no less than -5°C
Temperature of exploitation
- 30 to 50°C
Tests
IEC 60 502
Flame retardancy
IEC 332-3, Category A
 
  
Construction data 2 Construction data 2XSEY-FR, A2XSEY-FR 6/10 k XSEY-FR, A2XSEY-FR 6/10 k
Number of
cond. and
nominal
cross section
Thickness of insulation
Thickness of sheath
Nominal cross-sec­tion of screen
Cable diameter approx.
2XSEY-FR
A2XSEY-FR
Mass of Cu appr.
Cable weight approx.
Mass of Al appr.
Cable weight approx.
N.mm2
mm
mm
mm2
mm
kg/km
kg
kg/km
kg
6/10kV
 
 
 
 
 
 
 
 
3x35rm/16  3,4 2.5 16 47.6 1010  3276  298 2619 
3x50rm/16
3,4
2.6
16
50.3
1363
3834
404
2923
3x70rm/16
3,4
2.7
16
54.4
1968
4784
584
3470
3x95rm/16
3,4
2.8
16
58.4
2732
5930
809
4103
3x120rm/16  3,4 2.9 16 61.6 3440  6923  1023  4627 
3x150rm/25
3,4
3.0
25
64.4
4245
8217
1257
5379
3x185rm/25 
 3,4
3.2
25
68.5
5311
9691
1579
6144
3x240rm/25
3,4
3.4
25
74.3
6981
11963
2071
7331