Cable construction
|
Construction
|
According to IEC 60502-1
|
Conductor
|
Cu wires, flexible class 5,
according to IEC 60228
|
Insulation
|
rubber compound Type HEPR
according to IEC 60502-1
on base HEPR rubber
|
Core identification |
according to VDE 0293 |
Inner Sheath
|
Flame retarding PVC compound
|
Outer Sheath
|
PVC compound fire retardant and
reduced corrosive gas emission
|
Color
|
Grey RAL 7035
|
|
Technical data
|
Conductor resistance at 20°C
|
According IEC 60228 class 5
|
Operating temperature max at the conductor max
|
+90oC in operation
+250oC in the event of a short circuit
|
Temperature minimum
|
0oC
|
Rated voltage Uo/U
|
0.6/1kV
|
Test voltage AC, 50 Hz
|
4kV
|
Minimum bending radius
|
4x cable diameter
|
Testing according: Flame test
|
Test class C according IEC 60332-3
|
|
Color coding
|
Number of cores
|
Color of conductors without yellow/green
|
Color of conductors with yellow/green
|
1
|
Black or other
|
-
|
2
|
blue; brown
|
-
|
3
|
brown, black, grey
|
yellow/green, blue, brown
|
4
|
blue, brown, black, grey
|
yellow/green, brown, black , grey
|
5
|
blue, brown, black, grey, black
|
yellow/green, blue, brown, black, grey
|
5 and above
|
black with number mark on cores
|
black with number mark on cores and yellow/green in the outer cover
|
|
|
Construction data FG7OR 600/1000 V
|
Number of conductors and nominal cross section
|
Outer diameter approx.
|
Mass of Cu
|
Mass of
cable
approx
|
Nxmm2
|
nom/mm
|
kg/km
|
kg/km
|
1x1,5
|
5.8
|
11.9
|
47.4
|
1x2,5
|
6.2
|
19.8
|
58.5
|
1x4,0
|
6.7
|
32.4
|
76.0
|
1x6,0
1x10
|
7.6
8.8
|
48.2
87.3
|
101.4
152.2
|
1x16
1x25
|
9.8
11.7
|
134.9
206.4
|
210.4
306.6
|
1x35
|
13
|
293.7
|
408.6
|
1x50
|
15.2
|
410.5
|
564.9
|
1x70
1x95
|
17.5
20
|
584.7
774.3
|
773.2
1003.6
|
1x120
1x150
|
21.4
24.3
|
988.6
1245.5
|
1243.9
1569.6
|
1x185
|
25.7
|
1507.7
|
1859.6
|
1x240
|
30.4
|
1976.3
|
2410.1
|
1x300
|
33.6
|
2498.0
|
2986.3
|
2x1,5
|
11.6
|
24.3
|
179.5
|
2x2,5
2x4.0
|
12.3
13.4
|
40.4
66.0
|
212.5
265.8
|
2x6.0
2x10
|
15.2
17.6
|
98.3
177.9
|
349.5
501.9
|
2x16
|
20
|
275.0
|
686.5
|
2x25
|
23.8
|
420.6
|
987.8
|
2x35
2x50
|
26.4
30.4
|
598.5 836.5
|
1278.2 1724.5
|
2x70
2x95
|
35.4
39.6
|
1191.6
1577.9
|
2371.3
2998.4
|
2x120
|
42.8
|
2014.8
|
3672.4
|
2x150
|
47.8
|
2538.3
|
4569.0
|
3x1,5
|
12.1
|
36.4
|
199.0
|
3x2,5
|
12.9
|
60.6
|
210.0
|
3x4,0
3x6,0
|
14.0
16.0
|
99.0
147.5
|
307.0
408.0
|
3x10,0
|
18.6
|
270.0
|
600.0
|
3x16,0
|
21.2
|
412.5
|
834.0
|
3x25,0
3x35,0
|
25.2
28.5
|
630.0
998.0
|
1210
1620
|
3x50,0
|
32.3
|
1255
|
2160
|
3x70,0
|
37.7
|
1788
|
2980
|
3x95,0
|
42.2
|
2370
|
3776
|
|
Construction data FG7OR 600/1000 V
|
Number of conductors and nominal cross section
|
Outer diameter approx.
|
Mass of Cu
|
Mass of
cable
approx
|
Nxmm2
|
nom/mm
|
kg/km
|
kg/km
|
3x120
|
45.7
|
3022
|
4650
|
3x150
|
51.5
|
3808
|
5840
|
3x185
|
54.9
|
4610
|
6920
|
3x240
|
65.4
|
6040
|
9200
|
4x1.5
|
12.9
|
48.5
|
225.6
|
4x2.5
4x4
|
13.7
15.0
|
81
132.0
|
277
360.0
|
4x6
|
17.2
|
197.0
|
483.0
|
4x10
|
20.1
|
356.0
|
720.0
|
4x16
4x25
|
22.9
27.5
|
550.0 840.0
|
990.0 1450.0
|
3x35+25
3x50+35
|
30.3
33.5
|
1110
1460.0
|
1990.0
2560.0
|
3x70+35
|
38.8
|
2090.0
|
3550.0
|
3x95+50
|
44.1
|
2790.0
|
4590.0
|
3x120+70
|
48.0
|
3620.0
|
5700.0
|
3x150+95
|
54.6
|
4600.0
|
7250.0
|
3x185+95
3x240+150
|
57.2
68.4
|
5400.0
7310.0
|
8330.0
11350.0
|
5x1.5
5x2.5
|
13.7
|
60.6
|
257
320
|
14.6
|
101.0
|
5x4.0
|
16.1
|
165.0
|
420.0
|
5x6,0
|
18.6
|
246.0
|
570.0
|
5x10,0
5x16,0
|
21.8
25.0
|
450.0
690.0
|
850.0
1200.0
|
7x1,5
7x2,5
|
14.6
15.7
|
85.0
142.0
|
297.0
376.0
|
10x1.5
|
17.6
|
122.0
|
410.0
|
10x2.5
|
19.0
|
202.0
|
530.0
|
12x1,5
|
18.0
|
145.5
|
450.0
|
12x2,5
|
19.5
|
242.0
|
580.0
|
19x1,5
19x2,5
|
20.6
22.4
|
230.0 380.0
|
605.0
805.0
|
24x1,5
|
24.0
|
290.0
|
770.0
|
24x2,5
|
26.0
|
485.0
|
1020.0
|
27x1.5
27x2.5
|
24.5
26.6
|
328.0 546.0
|
820.0 1105.0
|
30x1,5
|
25.3
|
365.0
|
890.0
|
30x2,5
|
27.5
|
607.0
|