N2XSH NA2XSH

Uo/U  -  6/10,12/20kV VDE 0276-622
Application
The single-core cables flame retardant with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 6/10; 12/20 kV and frequency 50 Hz. The cables are manufactured with sheaths of halogen free flame retardant materials.
 
They are suitable for use in distribution installations, electric power stations and substations for fixed indoor assembly in cable ducts and conduits, over shelves and grilles.They should not be laid directly underground or in water. The cables with halogen free materials are with low halogen free smoke emission and corrosivity.The cables should not be laid in or near nuclear stations
 
Cable construction
Construction
according to DIN VDE 0276-622
Conductor
Cu and Al stranded compacted, wires according to IEC 60228 cl.2 and VDE 0295 cl.2
Inner semi-conductive layer
semi-conductive XLPE compound
Insulation
XLPE compound
Outer semi-conductive layer
semi-conductive XLPE compound and semi-conductive tape
Metal screen
Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm.
Separating layer
layer of plastic tape
Sheath
halogen free compound, flame retardant type HM4 to VDE 0276-622
Color
black
Technical data
Conductor resistance at 20°C
According to IEC60228 class 2 and VDE 0295 class 2
Operating temperature
90°C continuous operation
Overload temperature
130°C /100h per year max./
Short circuit temperature
250°C /5 s max/
Nominal voltage Uo/U:
6.35/11 kV
Highest system voltage Uo/U, no more than
6/10 kV;       12/20 kV 12 kV;           24 kV
Test voltage Uo/U
AC (≈) - 5 min
DC (=) - 15 min
6/10    12/20 kV
21 kV; 42 kV
67 kV; 134 kV
Bending radius, min Temperature of laying
15xD cable no less than -5°C
Temperature of exploitation Tests
-30 to 50∞— VDE 0276-622
-flame retardant
VDE 0276-622(VDE 0472-804 method C) - IEC 332-3/B
-corrosivity of combustion gases
-pH
min. 4.3
- conductivity
max. 100µS/cm
-density of smoke gases
VDE 0276-622 method to VDE0472-816
 
Construction data N2XSH, NA2XSH6/10; 12/20 kV
Number of
conductors
and nominal
cross section
Thickness of
insula­tion
Thickness of
sheath
Nominal cross-section of screen
Cable diameter approx.
N2XSH
 NA2XSH
Mass of
Cu approx
Mass of
cable
approx.
Mass of
Al approx.
Mass of
Cu approx.
Mass of
cable
approx.
 min
max
Nxmm2
mm
mm
 
mm
mm
kg/km
kg/km
kg/km
kg/km
kg/km
6/10 kV
 
 
 
 
 
 
 
 
 
 
1x35km/16  3,4 2,5 16 23 28 493 1145  94 176 922
1x50km/16
3,4
2,5
16
24
29
604
1297
127
176
996
1x70km/16
3,4
2,5
16
26
31
793
1550
183
176
117
1x95km/16
3,4
2,5
16
27
32
1033
1854
254
176
1251
1x120km/16
3,4
2,5
16
29
34
1255
2128
321
176
1371
1x150km/25
3,4
2,5
25
30
35
1596
2524
394
265
1587
1x185km/25  3,4 2,5 25 32 37 1930  2922  495 265 1752 
1x240km/25
3,4
2,5
25
34
39
2454
3536
649
265
1996
1x300km/25
3,4
2,5
25
36
41
2980
4149
812
265
2245
1x400km/35
3,4
2,5
35
40
45
3836
5117
1043
363
2688
1x500km/35
3,4
2,5
35
43
48
4807
6209
1374
363
3192
12/20 kV
 
 
 
 
 
 
 
 
 
 
1x35km/16
5,5
2,5
16
27
32
493
1372
94
176
1148
1x50km/16  5,5 2,5 16 28 33 604 1531  127 176 1230 
1x70km/16
5,5
2,5
16
30
35
793
1795
183
176
1362
1x95km/16
5,5
2,5
16
31
36
1033
2110
254
176
1507
1x120km/16
5,5
2,5
16
33
38
1255
2394
321
176
1636
1x150km/25
5,5
2,5
25
34
39
1596
2799
394
265
1862
1x185km/25
5,5
2,5
25
36
41
1930
3208
495
265
2038
1x240km/25  5,5 2,5 25 39 44 2454  3837  649 265 2298 
1x300km/25
5,5
2,5
25
41
46
2980
4466
812
265
2562
1x400km/35
5,5
2,5
35
44
49
3836
5478
1043
363
3049
1x500км/35
5,5
2,5
35
47
52
4807
6613
1374
363
3543