Home  »  Low voltage power cables, halogen free, flame retardant  »  2XSsH/( N )2XSsH 2XSH/( N )2XSH

2XSsH/( N )2XSsH 2XSH/( N )2XSH

Uo/U - 0.6/1 kV IEC 60 502-1 and VDE 0276-604 (HD 604 S1)
The power cables flame retardant, with low halogen free smoke emission and corrosion at fire conditions are suitable for use in elec­trical installations for nominal voltage 0.6/1kV in: 
 
important objects - power stations (nuclear, thermal), transformer substations, metro, airport, public buildings - hospitals, hotels, the­aters, cinemas, public and commercial centers, places with great concentration of people and material values whose safety in case of fire should be guaranteed.
 
The cables can be laid indoor, in air or in concrete. Direct laying underground or in water is not allowed.
Cable construction
Construction
According to VDE 0276-604
Conductor
Cu wires according toIEC 60228
Insulation
XLPE compound
2XI1 (DIX8) to VDE 0276-604
Core identification
according to VDE 0276-604 and VDE 0293
Inner sheath
halogen free compound
Metal screen
for 2XSsH - copper breid for 2XSsH - copper tape
Sheath
halogen free compound, flame retardant type HM4(LTS 1)
Color
Black
Technical data
Conductor resistance at 20°C
according to VDE 0295 (IEC60228) cl.1 or 2
Operating temperature
90°C continuous operation
Overload temperature
130°C /100h per year max/
Short circuit temperature Nominal voltage Uo/U
250°C/ 5 s max./. 0.6/1 kV
Highest system voltage
no more than 1.2 kV
Test voltage AC - 5 min
between cores - 3.5 kV
Bending radius, min
6xD cable
Temperature of laying Temperature of exploitation
no less than 0°C -30 to 50°C
Tests
-flame retardant -corrosivity of combustion gases and conductivity
IEC 60502-1 and VDE 0276-604 VDE 0472 p804/C( IEC 332-3/C and B)
pH - min 4.3; -max100 S/cm
VDE 0472p813 (IEC 60754-1 and 2)
-density of smoke gases
VDE 0472p816 (IEC 61034-1 and 2)