2XBH/A2XBH

Uo/U - 0.6/1 kV IEC 60502-1 and VDE 0276-604 (HD 604 S1)
Application:
The power cables flame retardant, with low halogen free smoke emission and corrosion at fire conditions are suitable for use in electrical installations for nominal voltage 0.6/1kV in:
 
important objects - power stations (nuclear, thermal), transformer substations, metro, airport, public buildings - hospitals, hotels, theaters, cinemas, public and commercial centers, places with great concentration of people and material values whose safety in case of fire should be guaranteed.
 
The cables can be laid indoor, in air or in concrete.
Direct laying underground or in water is not allowed.
 
Cable construction
Construction
According to IEC 60502-1
Conductor
 
Cu solid or stranded wires class 1
or 2 according to IEC 60228
Insulation
XLPE compound
Identification
of cores
color code acc.
to VDE 0276-604
Inner sheath
halogen free compound
Armour
 
two steel tapes or two
galvanized steel tapes
Sheath
 
halogen free compound, flame
retardant type HM4( LTS 1 )
Color
black
Technical data
Conductor resistance Operating temperature
According to IEC 60228 90°C
Overload temperature
130°C/100h per year
Short circuit temperature
250°C ( 5 sec.)
Nominal voltage
0.6/1 kV
Highest system voltage
1.2 kV
Test voltage, AC 50 Hz
4.0 kV
Bending radius
 
single core
15 x Dcable
multicore
15 x Dcable
Temperature of laying
no less than 0°C
Temperature of exploitation
-30 to 70°C
Tests
-flame retardant
IEC 60502-1 and VDE 0276-604 VDE 0472 p804/ ­ ( IEC 332-
3/C and B)
-corrosivity of combustion
 
gases and conductivity
 
pH - min 4.3; σ-max100|aS/cm
VDE 0472p813 (IEC 60754-1and2
-density of smoke gases
VDE 0472p816 (IEC 61034-1and2)
asdfColor coding
Single core Double core
- black or yellow-green
- blue and brown or yellow-green and black
3 - core
4 - core
5 - core
Multiple core
brown; black; grey
or
yellow/green ; blue; brown
blue; brown; black; grey
or
yellow/green
; brown; black ;grey
blue ; brown;
black; grey
black
or
yellow/green
; blue;
brown;
black; grey
black with num­ber mark on cores
or
black with num­ber mark on
cores and yel­low/green core in
the outer cover
Construction data 2XBH
Number of
conductors
and nominal cross section
Types of 
ductors
Cable diameter
approx.
Mass
of
core approx.
Mass of
cable
approx.
N x mm2
 
mm2
mm
kg/km
 
 
 
 
 
5x4,0
re
19,6
187
590
5x6,0
re
21,0
279
715
5x10
re
23,2
470
955
5x16
re
25,7
744
1270
5x25
5x35
rm
rm
31,7
34,9
1213 1683
1925 2455
5x50
5x70
rm
rm
40,1
45,3
2271 3280
3390 4455
7x1,5
re
16,9
100
420
8x1,5
re
18,2
114
485
10x1,5
re
19,9
142
575
12x1,5
re
20,4
171
610
14x1,5
16x1,5
re
re
21,2
22,1
199 227
675
725
19x1,5
re
23,0
270
795
20x1,5
re
24,0
284
855
21x1,5
re
24,0
299
865
24x1,5
re
26,1
341
1005
27x1,5
30x1,5
re
re
26,6
27,5
384 426
1055 1125
37x1,5
7x2,5
re
re
29,4
18,0
526 163
1300 505
8x2,5
re
19,6
186
590
10x2,5
re
21,5
232
705
12x2,5
14x2,5
re
re
22,0
22,9
279 325
760
830
16x2,5
19x2,5
re
re
23,9
25,0
372 441
905 1005
20x2,5
re
26,1
464
1080
21x2,5
re
26,1
488
1095
24x2,5
re
28,6
557
1290
27x2,5
re
29,2
627
1360
30x2,5
37x2,5
re
re
30,2
32,3
697 859
1465 1700
7x4,0
8x4,0
re
re
20,9
22,9
261 299
700
825
10x4,0
re
25,4
373
1030
7x6,0
re
22,4
391
885
8x6,0
10x6,0
re
re
19,5
27,4
447 559
1045 1270