U 1000 AR2V

Uo/U  - 0.6/1 kV NF C 32-321
Appliccation
These cables are used for distribution and supply of consumers with electrical power with nominal voltage 0.6/1kV and frequency 50 Hz in industrial installations and urban networks.
 
They are suitable for fixed indoor assembly in cable ducts, tunnels and conduits, over shelves and grilles, directly underground in ditch and outdoor under shelters providing the conditions determined for the type of cable.
 
Cable construction
Construction
According to NF C 32-321
Conductor
Aluminum wires acc. NF C 32-321
- single core circular class 2,
2.5 to 35mm2
- stranded class 2 round and
- sector,     35 to240mm2
Insulation
XLPE compound
Filling
- up to 6 cores - PVC filling
 
- 7 cores and more - polyester tape
Sheath
PVC compound
Color
black
Technical data
Conductor resistance at 20°C
According to NF C 32-321
Operating temperature
90°C continuous operation
Overload temperature
130°C /100h/per year max./
Short circuit temperature
250°C /5 s max./
Nominal voltage Uo/U:
0.6/1 kV
Highest system voltage
1.2 kV
Temperature range
laying and installing
exploitation and storage
 
-5°C to +60°C
-25°C to +70°C
Bending radius, min. approx.
10 x D cable
Color coding
Single core Double core
-black or yellow/green
- blue and brown or yellow-green
and black
3-core
4-core
5-core
Multiple core
brown black grey
or
yellow/
green
blue
brown
 
 
blue
brown black grey
or
yellow/
green
brown
black
grey 
blue
brown black grey black
or
yellow/green
blue
brown
black
grey
black with number mark on cores
or
black with number mark
on cores and
yellow/green core in the
outer cover