EXVB

Uo/U  - 0.6/1 kV NBN C 33-322  /  NBN C 30-004
Cu conductors • XLPE insulation • PVC filling • PVC sheath
Application
These cables are used for distribution and supply of consumers with electrical power with nominal voltage 0.6/1kV and frequency 50 Hz in industrial installations and urban networks.
 
They are suitable for fixed indoor assembly in cable ducts, tunnels and conduits, over shelves and grilles, directly underground in ditch and outdoor under shelters providing the conditions determined for the type of cable.
 
Cable design
Construction
According to NBN C 33-322
Conductor
Cu according to NBN C 33-322
(IEC 60228):
-rm   class 1          1.5 to 16mm2
-rm   class 2          1.5 to 500mm2
Insulation
XLPE compound
Inner
sheath
tape or extrusion
Sheath
PVC compound
Color
black
Technical data
Conductor resistance at 20°C
IEC 60228
Operating temperature
90°C continuous operation
Overload temperature
130°C /100h/per year Max./
Short circuit temperature
250°C /5 s max./
Nominal voltage Uo/U:
0.6/1 kV
Highest system voltage
1.2 kV
Temperature range
laying and installing
exploitation and storage
 
-5°C to +60°C
-25°C to +70°C
Bending radius, min. approx.
12 x D cable
Construction
Core color
4x
Blue / brown / black / black
 
Construction data EXVB 0.6/1 kV
Number of conductors and nominal cross
section
Shape
Cable diameter approx.
Cu weight
Cable weight approx.
N.mm2
 
mm
kg/km
kg/km
4x10
re
18.5
363
695
4x16
rm
21.0
592
1002
4x25
rm
25.5
925
1445