Home  »  Low voltage power cable with PVC insulation  »  (N)AY2Y-0 (N)AY2Y-J

(N)AY2Y-0 (N)AY2Y-J

Uo/U - 0.6/1 kV Similar to VDE 0276 part 603
Application
(N)AY2Y is used in power plants industrial and switching installations, in secondary distribution networks and other.These cables are preferentially used in outdoor applications, for indoor instalations, in the open air, underground and in water where mechanical damage is not anticipated.
Cable construction
Construction
According to VDE 0276 part 603
Conductor
solid or multi-strand Al wires class 1
or 2 acc. VDE 0295 (IEC 60228)
Insulation
PVC type DIV4 acc. VDE0276
Core identification
 according to VDE 029
Sheath
PE type DMP 2 acc. VDE 0276
Color
black
Technical data
Conductor resistance at 20°C
According to VDE 0295 class 1 or 2 (IEC 60228)
Max. conductor temperature
+70°C
Max. short circuit temperature
+160°C, not more than 5 sec
Rated voltage Uo/U
0.6/1 kV
Test voltage
AC - 4 kV     50 Hz
Bending radius
-single core
-multi core
 
15 cable diameter
12 cable diameter
Color coding
Single core
Double core
-black, or yellow/green
-light blue and brown or yellow-green and black
3 - core
4 - core
5 - core
brown
black
grey
or
yellow/green
light blue
brown

 

 
light blue
brown
black
grey
or
yellow/green
brown
black
grey
light blue
brown
black
grey
black
or
yellow/green
light blue
brown
black grey
Construction data (N)AY2Y o/j   0.6/1 kV
Number of wires and nominal cross sec­tion
Shape
Outer diameter of cable approx.
Al weight
Cable weigh approx
 
N.mm2
 
mm
kg/km
kg/km
 
1 x 25,0
re
11,5
70
159
1 x 35,0
re
12,5
97
195
1 x 50,0
re
13,9
131
249
1 x 50,0 rm 15,1 135 255 
1 x 70,0
rm
16,1
195
339
1 x 95,0 rm 18,2 270 447 
1 x 120,0
rm
20,0
341
525
1 x 150,0
rm
22,0
419
631
1 x 185,0
rm
24,1
526
780,
1 x 240,0 rm 27,1 690 986 
1 x 300,0
rm
29,1
863
1233
1 x 400,0 rm 33,1 1109  1531 
1 x 500,0
rm
37,1
1461
2019
2 x 25,0
re
20,4
140
276
2 x 35,0
re
22,3
194
346
2 x 50,0
re
25,3
261
451
2 x 35,0
rm
23,4
199
358
2 x 50,0 rm 26,5 269 507 
2 x 70,0
rm
30,0
390
781
2 x 95,0
rm
34,6
539
1045
3 x 25,0
re
21,7
210
475
3 x 35,0
re
23,6
291
585
3 x 50,0
re
26,8
392
763
3 x 50,0 sm 25,8 404 839 
3 x 70,0
sm
29,2
584
1066
3 x 95,0 sm 33,8 809  1441 
3 x 120,0
sm
36,0
1023
1710
3 x 150,0
sm
39,8
1257
2074
3 x 185,0
sm
43,1
1579
2546
Construction data (N)AY2Y o/j   0.6/1 kV
Number of wires and
nominal cross sec­tion
 Shape
Outer diameter
of cable approx.
Al
weight
Cable weight
 
approx.
N.mm2
 
mm
kg/km
kg/km
3 x 240,0
sm
48,2
2071
3267
3 x 50,0+25
re+re
28,0
462
940
3 x 50,0+25
sm+rm
31,2
474
1003
3 x 70,0+35 sm+rm  36,0 684  1337 
3 x 95,0+50
sm+rm
40,2
944
1738
3x120,0+70  sm+rm  43,2 1218  2050 
3x150,0+70
sm+rm
48,0
1452
2509
3 x 185,0+95
sm+rm
52,3
1848
3096
3x240,0+120
sm+rm
58,7
2412
3939
3x300,0+150  sm+rm  64,3 3008  4801 
4 x 25,0
re
23,8
281
681
4 x 35,0 re 26,2 388  832 
4 x 50,0
re
29,8
522
1129
4 x 50,0
sm
29,2
539
1081
4 x 70,0
sm
33,6
779
1415
4 x 95,0
sm
38,2
1079
1855
4 x 120,0
sm
41,2
1364
2182
4 x 150,0 sm 45,2 1676  2736 
4 x 185,0
sm
49,6
2105
3565
4 x 240,0
sm
55,7
2762
4300
4 x 300,0
sm
61,3
3452
5259
5 x 25,0
re
26,1
351
750
5 x 35,0
re
28,9
485
1009
5 x 50,0 re 32,8 653  1352 
5 x 25,0
rm
27,4
360
836
5 x 35,0 rm 30,4 497  1094 
5 x 50,0
rm
34,6
673
1463
5 x 70,0
rm
39,2
974
1846
5 x 95,0
rm
45,2
1349
2481