Home  »  Low voltage power cable with PVC insulation  »  E-AY2Y-0 E-AY2Y-J

E-AY2Y-0 E-AY2Y-J

Uo/U - 0.6/1 kV HD 603 S1 part 3A
Application
E-AY2Y is used in power plants industrial and switching installations, in secondary distribution networks and other.These cables are preferentially used in outdoor applications, for indoor instalations, in the open air, underground and in water where mechanical damage is not anticipated
Cable construction
Construction
According to VDE 0276 part 603
Conductor
solid or multi-strand Al wires class 1
or 2 acc. VDE 0295 (IEC 60228)
Insulation
PVC type DIV1 acc. HD 603 S1
Core identification
according to VDE 0293
Sheath
PE type DMP 2 acc. VDE 0276
Color
black
Technical data
Conductor resistance at 20°C
According to VDE 0295 class 1 or 2 (IEC 60228)
Max. conductor temperature
+70°C
Max. short circuit temperature
+160°C, not more than 5 sec
Rated voltage Uo/U
0.6/1 kV
Test voltage
AC - 4 kV     50 Hz
Bending radius
-single core
-multi core
 
15 cable diameter
12 cable diameter
Color coding
Single core Double core
-black, or yellow/green
-blue and brown or
yellow -greenand black
3 - core
4 - core
5 - core
brown/black grey
or
yellow/green blue/brown
blue/brown/ black/grey
or
yellow/green
brown/black/
grey
blue/brown
black/grey/
black
or
yellow/green blue/brown black/grey
Construction data E-AY2Y o/j   0.6/1 kV
Number of wires and nominal cross sec­tion
Shape
Outer diameter of cable approx.
Al weight
Cable weight approx.
N.mm2
 
mm
kg/km
kg/km
1 x 25,0
re
11,5
70
159
1 x 35,0 re 12,5 97 195
1 x 50,0
re
13,9
131
249
1 x 50,0
rm
15,1
135
255
1 x 70,0
rm
16,1
195
339
1 x 95,0 rm 18,2 270 447
1 x 120,0
rm
20,0
341
525
1 x 150,0 rm 22,0 419 631
1 x 185,0
rm
24,1
526
780,
1 x 240,0
rm
27,1
690
986
1 x 300,0
rm
29,1
863
1233
1 x 400,0
rm
33,1
1109
1531
1 x 500,0
rm
37,1
1461
2019
2 x 25,0 re 20,4 140 276
2 x 35,0
re
22,3
194
346
2 x 50,0
re
25,3
261
451
2 x 35,0
rm
23,4
199
358
2 x 50,0
rm
26,5
269
507
2 x 70,0
rm
30,0
390
781
2 x 95,0
rm
34,6
539
1045
Construction data E-AY2Y o/j   0.6/1 kV
Number of
wires and
nominal
cross sec-
Shape
Outer diameter of cable approx.
Al weight
Cable weight approx.
N.mm2
 
mm
kg/km
kg/km
3 x 25,0
re
21,7
210
475
3 x 35,0 re 23,6 291  585
3 x 50,0
re
26,8
392
763
3 x 50,0
sm
25,8
404
839
3 x 70,0
sm
29,2
584
1066
3 x 95,0 sm 33,8 809  1441 
3 x 120,0
sm
36,0
1023
1710
3 x 150,0 sm 39,8 1257  2074 
3 x 185,0
sm
43,1
1579
2546
3 x 240,0
sm
48,2
2071
3267
3 x 50,0+25
re+re
28,0
462
940
3 x 50,0+25
sm+rm
31,2
474
1003
3 x 70,0+35
sm+rm
36,0
684
1337
3 x 95,0+50  sm+rm  40,2 944  1738 
3x120,0+70
sm+rm
43,2
1218
2050
3 x 150,0+70
sm+rm
48,0
1452
2509
3 x 185,0+95
sm+rm
52,3
1848
3096
3x240,0+120
sm+rm
58,7
2412
3939
3x300,0+150
sm+rm
64,3
3008
4801