AYY-0 AYY-J

Uo/U  - 0.6/1 kV IEC 60502-1
Al conductors • PVC insulation • PVC sheath
Application
AYY is used in power plants industrial and switching installations, in secondary distribution networks and other.These cables are preferentially used in outdoor applications, for indoor instalations, in the open air, underground and in water where mechanical damage is not anticipated.
Cable construction
Construction
According to IEC 60502-1
Conductor
solid or multi-strand Al wires class 1
or 2 acc. IEC 60228
Insulation
PVC type PVC/A acc. to IEC 60502
Core identification
single core-black, multiple core
according to VDE 0293
Sheath
PVC type ST1 acc. IEC 60502
Color
black
Technical data
Conductor resistance at 20°C
According to IEC 60228 class 1 or 2
Max. conductor temperature
+70°C
Max. short circuit temperature
+160°C, not more than 5 sec
Rated voltage Uo/U
0.6/1 kV
Test voltage
3.5 kV
Bending radius
-single core
-multi core
 
15 cable diameter
12 cable diameter
Flame test
IEC 332 part 1
Construction data AYY o/j   0.6/1 kV
Number of wires and
nominal cross sec­tion
N.mm2
Shape

 
Outer diameter
of cable approx.
mm
Al
weight
kg/km
Cable
approx.
kg/km
4 x 16,0
re
20.3
180
460
4 x 25,0
rm
24.9
270
670
4 x 50,0
sm
28.9
520
1180
4 x 70,0
4 x 95,0
sm
sm
33.2
37.6
760 1060
1390 1860
Construction data AYY o/j   0.6/1 kV
Number of wires and
nominal cross sec­tio
N.mm2
Shape

 
Outer diameter
of cable approx.
mm
Al
weight
kg/km
Cable weight
approx.
kg/km
4 x 120,0
sm
40.6
1340
2210
4 x 150,0
sm
45.4
1650
2710
4 x 185,0
sm
49.8
2100
3320
4 x 240,0
sm
55.9
2720
4110