Technical data
|
Conductor resistance at 20°C
|
According to IEC60228 class 2 and VDE 0295 class 2
|
Operating temperature
|
90°C continuous operation
|
Overload temperature
|
130°C/100h per year max./
|
Short circuit temperature Nominal voltage Uo/U
|
250°C /5 s max./ 26/45 kV 38/66 kV
|
Highest system voltage Uo/U, no more than
|
52 kV; 72.5 kV
|
Test voltage Uo/U
AC (≈) - 30 min
|
26/45 kV 38/66 kV 65 kV 90 kV
|
Partial discharge level
at 2*Uo Bending radius, min
|
max. 5pC
15x D cable
|
Temperature of laying
Temperature of exploitation
|
no less than (-5°C)
-30 to 50°C
|
Tests
|
according to IEC 60840 according to VDE 0276-632
|